Cooling Tower Fill Media

Surya D-15 S Type Drift Eliminator

The D-15 S Type is a cellular PVC drift eliminator that captures water droplets from the exhaust air, cutting drift loss to 0.001% of total circulating water with a very low pressure drop. It withstands temperatures up to 55 °C and suits small and medium counterflow and crossflow cooling towers.

Surya D-15 cellular drift eliminator block in white PVC, showing its honeycomb cell structureD-15 S
Overview

D-15 drift eliminator. Less loss. Low drag.

The D-15 S Type is a cellular PVC drift eliminator that captures water droplets from the exhaust air, cutting drift loss to 0.001% of total circulating water with a very low pressure drop. It withstands temperatures up to 55 °C and suits small and medium counterflow and crossflow cooling towers.

Key features

  • Cellular design: drift loss of 0.001% of circulating water
  • Very low pressure drop (drag coefficient 2.2)
  • Handles face velocities up to 4.5 m/s
  • Withstands temperatures up to 55 °C
  • Shipped as nested sheets and glued at site into blocks
  • Low transportation cost
D-15 S – Technical specification
TypeCellular drift eliminator, D-15 S
Material (MOC)PVC
Max. face velocity4.5 m/s
Drag coefficient2.2
Distance between supportsMax. 600 mm
Width of support10 mm
Drift loss0.001% of total circulating water
Max. operating temperature55 °C
Tower typeSmall & medium counterflow and crossflow
Supply formNested sheets, glued at site into blocks
Pack depth / block sizeAvailable on request*

* Typical, indicative value; please confirm against the batch certificate or with our team for your application.

D-15 S Type Drift Eliminator data sheet

One-page PDF with features, specifications and applications.

Data sheet PDF, 138 KB

Applications

  • Small and medium counterflow cooling towers
  • Small and medium crossflow cooling towers
  • Reducing water and treatment-chemical loss
  • Drift eliminator replacement and retrofits
Need a different specification?

Talk to our team about your requirement

Share your tower type, water quality and dimensions and our engineers will recommend the right fill or eliminator.

Related products

More cooling tower fill media

Enquiry

Enquire About D-15 S Type Drift Eliminator

Tell us your requirement for D-15 S Type Drift Eliminator and our team will get back to you.

  • Manufacturing locationsVill. Dharampur, Baddi, Distt. Solan, Himachal Pradesh 173205
    Vill. Nangal, Swarghat Road, Nalagarh, Distt. Solan, Himachal Pradesh 174101
  • Phone[Official number]
  • Emailsuryavinyl@gmail.com

Fields marked * are required.